Home > Capacitor, Fuse, Circuit Breaker > FSC 5925 > 5925-00-626-4343

5925-00-626-4343, 5925006264343 NSN Information

Request for Quote

Manufacturer Part Number(s):AP12-1-6-2-153, HB2Z1-68, M39019-3-68, MILC39019-3, SM33-15-250VAC60C1, SM33-15-60-1

FSC NIIN ITEM NAME
5925 006264343 CIRCUIT BREAKER
INC ESDC HMIC
0013 P

5925-00-626-4343 MCRD (Master Cross Reference Data)

Mfg. Part # Mfg. Name CAGE RNCC RNVC ISC MSDS SADC DAC HCC
AP12-1-6-2-153 SENSATA TECHNOLOGIES MARYLAND INC 81541 C 1 E
HB2Z1-68 EATON CORP 74193 C 1 E
M39019-3-68 MILITARY SPECIFICATIONS 81349 2 2 E
MILC39019-3 MILITARY SPECIFICATIONS 81349 4 1 E
SM33-15-250VAC60C1 EATON CORP 74193 C 1 E
SM33-15-60-1 EATON CORP 74193 C 1 E

5925-00-626-4343 Characteristics

MRC Requirement Statement Characteristics
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 300.0 AC ALL LOCATIONS
ADAT BODY WIDTH 1.281 INCHES MAXIMUM
CPRJ TRIP RELEASE METHOD MAGNETIC ALL LOCATIONS
CQJX NOMINAL THREAD SIZE 0.375 INCHES
CPRP ULTIMATE TRIP TIME PER POLE IN SECONDS 3.000 MINIMUM AND 60.000 MAXIMUM ALL LOCATIONS
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.906 INCHES MAXIMUM
ABXD BUSHING LENGTH 0.380 INCHES MAXIMUM
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
AXHR MOUNTING FACILITY TYPE AND QUANTITY 1 THREADED BUSHING
SR-1 SPEC/STD CONTROLLING DATA
ADTV CASE MATERIAL METAL
APNQ III ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 0.500 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
THSD THREAD SERIES DESIGNATOR UNEF
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
SR-1 NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCE MILC39019-3
CPRQ RESET METHOD MANUAL
SR-1 DEFINITIVE GOVERNMENT SPEC/STD REFERENCE M39019-3-68
AAJE THREAD PITCH DIAMETERS 0.3503 TO 0.3537 INCHES
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.828 INCHES MAXIMUM
BBRJ III SPECIAL HANDLING FEATURE MAGNETIC
ZZZK SPECIFICATION/STANDARD DATA 81349-MIL-C-39019/3 GOVERNMENT SPECIFICATION
AFJN III FRAGILITY FACTOR MODERATELY RUGGED
ADAQ BODY LENGTH 1.562 INCHES MAXIMUM
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 15.0 AMPERES AC ALL LOCATIONS
SR-1 MANUFACTURERS CODE 81349
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.625 INCHES NOMINAL
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CMLP THREAD QUANTITY PER INCH 32
BBRG III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 115.0 ALL LOCATIONS
AKPX POLE QUANTITY 2
TTQY TERMINAL TYPE AND QUANTITY 4 WIRE HOOK
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND HERMETICALLY SEALED
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE