Home > Capacitor, Fuse, Circuit Breaker > FSC 5925 > 5925-00-024-0864

5925-00-024-0864, 5925000240864 NSN Information

Request for Quote

Manufacturer Part Number(s):651322, 659001CB1, 72-317-1MG6, 72-317-1NG6

FSC NIIN ITEM NAME
5925 000240864 CIRCUIT BREAKER
INC ESDC HMIC
0013 P

5925-00-024-0864 MCRD (Master Cross Reference Data)

Mfg. Part # Mfg. Name CAGE RNCC RNVC ISC MSDS SADC DAC HCC
651322 THERMO JARRELL ASH CORP 05234 5 2 C
659001CB1 THERMO JARRELL ASH CORP 05234 3 2 C
72-317-1MG6 EATON CORP 74193 5 9 C
72-317-1NG6 EATON CORP 74193 C 1 C N

5925-00-024-0864 Characteristics

MRC Requirement Statement Characteristics
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM
PKWT III UNPACKAGED UNIT WEIGHT 14.000 OUNCES
ADAQ BODY LENGTH 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
APNQ III ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRW ACTUATOR FUNCTION TRIP-RESET
TTQY TERMINAL TYPE AND QUANTITY 8 THREADED STUD
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 AC ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP FIRST LOCATION SERIES TRIP SECOND LOCATION RELAY TRIP THIRD LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 3.5 AMPERES AC FIRST LOCATION 3.5 AMPERES AC SECOND LOCATION 500.0 MILLIAMPERES AC THIRD LOCATION
CPRQ RESET METHOD MANUAL
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND MOISTURE RESISTANT
BBRJ III SPECIAL HANDLING FEATURE MAGNETIC
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
AFJN III FRAGILITY FACTOR MODERATELY RUGGED
AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 THREADED HOLE
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
THSD THREAD SERIES DESIGNATOR UNC
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
ADTV CASE MATERIAL PLASTIC
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 3 TOGGLE
AJEC BOSS HEIGHT 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC ALL LOCATIONS
CMLP THREAD QUANTITY PER INCH 32
ADAT BODY WIDTH 2.240 INCHES MINIMUM AND 2.260 INCHES MAXIMUM
BBRG III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CQJX NOMINAL THREAD SIZE 0.138 INCHES
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM
AKPX POLE QUANTITY 3
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 0.300 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE